On 28 July 2009 EPA perimeter air monitoring for VOCs and HF continues to reflect a non-detect. CITGO continues to discharge the seawater used in fire fighting and vapor suppression through Outfall 004, a storm water outfall, at approximately 3,500 gpm. CITGO sampled Outfall 004 at 4 hour intervals for the parameters for storm water plus pH and fluoride. CITGO reports the results are within the NPDES permit limit, with fluoride running equal to and less than 10 ppm. TCEQ is grabbing split samples twice a day and analyzing for the waste water parameters in CITGO’s discharge permit. At 1730 hours CITGO discontinued the usage of saltwater for vapor suppression. Immediately following, CITGO entered the unit to confirm that the leaks were secured, repaired and replaced elements in the unit’s internal monitoring system. At 2025 hours the all clear was sounded by CITGO and decontamination of the unit’s exterior began.
On 29 July 2009 CITGO is depressurizing the unit and is preparing to de-inventory the unit. De-inventory is projected to begin tomorrow and last 2 to 3 days. Once the unit is de-inventoried the internal decontamination will begin with an acid wash, followed by a caustic wash, and completed by a neutralization wash. The internal decontamination is estimated to last 1 to 3 days. There is an estimated 150,000 barrels of fresh water, used during vapor suppression efforts, stored in the secondary containment of Equalization Tanks 116 and 117. The stored fresh water was previously treated with soda ash to adjust the pH from around 2 to 7. CITGO is considering options for disposal of the treated fresh water through additional methods. The fresh water, used during vapor suppression efforts, stored in Equalization Tanks 116 and 117 is being treated with the plant waste and being discharged with elevated fluoride concentrations from Outfall 001.
|