EPA OSC Kevin Misenheimer and START contractor TTEMI mobilized to the site to assist with the airborne detection of mercury using the Lumex mercury vapor analyzer and to provide guidance regarding clean up measures.
OSC Misenheimer and START arrived on scene at approximately1530 CST on 17 November. A site briefing was given by Unified Command (SOSC Shirley, EMA Steed and WTP operator Michael Smith). A health and safety briefing was also conducted with START and MDEQ contractor USES. Based on these briefings, it was determined that additional assessment using the Lumex vapor analyzer was required to determine the effectiveness of clean up actions to date.
EPA and START conducted a Level C entry to monitor mercury vapor levels using the Lumex. Monitoring was conducted in the stairwell, control room, laboratory, and several offices. Mercury vapors were measured at head level at concentrations of 34,000 ng/m3 in the stairwell, 29,000 ng/m3 in the laboratory, 22,500 ng/m3 in the control room and 36,000 ng/m3 in the second floor hallway. In addition to these levels detected at head level, higher readings (up to 53,000 ng/m3) were observed at floor level on the main stairwell and around the first floor entrance to the building.
Based on this data collected by EPA, MDEQ directed USES to continue clean up actions to remove additional sources of mercury and to reduce vapor concentrations in the areas of concern. USES again wiped down all surfaces with mercury sorbent material and cleaned the metal on the stairs using an acid solution. Once these activities were completed, EPA and START conducted another round of air monitoring to evaluate the effectiveness of clean up actions. Mercury vapors were measured at head level at concentrations of 7,000 ng/m3 in the stairwell, 6,700 ng/m3 in the laboratory, 5,100 ng/m3 in the control room and 2,000 ng/m3 in the second floor hallway.
MDEQ then directed USES to heat and vent the building. This procedure of heating and venting of the building was repeated several times. START then conducted one final entry to monitor mercury vapors using the Lumex. Mercury vapors were measured at head level at concentrations of 8,000, 5,000 and 2,000 ng/m3 in the stairwell, 1,000 ng/m3 in the laboratory and 2,100 ng/m3 in the control room. Based on these results, EPA and MDEQ determined that clean up actions were complete and that the City of Hattiesburg could re-occupy the building to conduct routine water treatment operations.
After consultation with FOSC Jones, USES placed hazardous and non-hazardous mercury contaminated material from the site into roll-off containers being used for the nearby Chapman Mercury Site. Waste was segregated into hazardous and non-hazardous roll-off containers. Hazardous waste consisted of approximately 15 bags of material and non-hazardous waste consisted of three chairs, several boxes and a printer. This material will be disposed of as a part of the final actions at the Chapman Mercury Site.
|