Site Description

See POLREP #1 for a description of the activities taken during the Emergency Response phase.


Current Activities

The following activities have taken place during this reporting period:

In order to determine the cause of the release, NCDENR Department of Water Quality (DWQ) conducted sampling at the site.  They collected three soil samples (including sediment from Moss Fork Creek) and two water samples, one upstream of the discharge and one downstream of the discharge).  They analyzed the samples for organics and the results area as follows:

SS-1:  Collected from the sediment near the discharge point - 330 ppm gasoline organics, 440 ppm diesel organics

SB-1:  Collected from a bore sample located adjacent to E. Caswell St. - 5.5 ppm gasoline organics, BDL for diesel

SB-2:  Collected from a bore sample located upstream of the stream sediment collection area - 31 ppm gasoline organics, 230 ppm diesel organics

DS-1:  Water Sample collected downstream of discharge - Minor hits for BTEX

US-1:  Water Sample collected upstream of discharge - No detectible volitiles

The results of this data show that the discharge is most likely a gasoline/diesel mixture, most likely from an underground storage tank at the Anson Mart property.  

The likely PRP, the owner of Anson Mart, has removed a small AST from behind the store that at one time held kerosene used for heating.  He also has been asked by the state UST program to perform a dye tracer study on his UST system to isolate the source of the possible leak.


Planned Removal Actions

Since the discharge is a mixture of gasoline and diesel from a UST, the rest of the removal will be handled by the State UST program.  This program plans to take enforcement action against the PRP if he neglects to perform tracer studies.  Once the location of the release is found and repaired, steps will be taken to remediate contaminated soil.


response.epa.gov/mossforkcreekmysteryspill